The MetalPan D-Fuser product is a fabric faced terminal diffusion device that includes a metal backpan for traditional installation method. Given the airflow patterns generated by the unique combination of permeable fabric and face shape, throw data provided include measurements for both the horizontal and vertical and positions for both end and side orientations. Select Flow Explanation

Performance tables include throw data for both SIDE and END direction. Throw is measured from the center location of the unit. To determine actual throw from side or end of device, deduct 1/2 of the length or width of the unit. Example: at 375 CFM, 8 feet of END Horizontal Throw is recorded to 50 fpm. Considering length of device, this reading is actually only 7 feet from the end of the unit.

 